VZF-12R Mid Mounted Vacuum Circuit Breaker Solid Sealed Load Switch Fuse 40kA
Contact me for free samples and coupons.
Whatsapp:0086 18588475571
Wechat: 0086 18588475571
Skype: sales10@aixton.com
If you have any concern, we provide 24-hour online help.
xName | VCB Circuit Breaker | Voltage | High Voltage |
---|---|---|---|
Rate Current | 630A-4000A | Space Current | 25kA-40kA |
Wide | 650mm-800mm | Life | 20000 Times |
Highlight | Mid Mounted Vacuum Circuit Breaker,Solid Sealed Vacuum Circuit Breaker,40kA Vacuum Circuit Breaker |
VZF-12R Mid - mounted solid - sealed load switch fuse combination appliance
Introduction
VZF-12R vacuum circuit breaker is suitable for reclosing operation and has high operation reliability and service life.
VZF-12R vacuum circuit breaker(general type) uses vertical insulators to protect against climate effects; And in the maintenance and maintenance aspect, usually only need to do the operation between or sexual cleaning or lubricating.
VZF-12R vacuum circuit breaker(pole type) adopts solid insulation structure-integrated seal pole, realized maintenance free.
The magnetic field produced by the coil and the magnetic field produced by the permanent magnet is superimposed and synthesized by the magnetic field. The magnetic core, together with the driving rod fixed on it, is operated by the synthetic magnetic force and the switch body is turned on and off at the specified speed. This mechanism is called a two-bit bistable structure because the moving iron core can be maintained without any energy consumption at the two ends of the journey. In the traditional electromagnetic mechanism, the moving core is kept at one end of the journey by the action of a spring, while at the other end of the journey, it is protected by a mechanical latch or electromagnetic energy. From the above, the permanent magnet actuator is a special combination of electromagnet and permanent magnet to achieve the traditional circuit breaker operating mechanism of all functions: permanent magnet instead of traditional .
Parameters
Item | Technical data | ||||||||||||
Rated voltage (KV) | 3.6 | 7.2 | 12 | 24 | 40.5 | ||||||||
Rated frequency(Hz) | 50 | ||||||||||||
Insulator(capacity) | insulating | Frequency withstand voltage 5 min (KV) | 25 | 32 | 42 | 68 | 100 | ||||||
Frequency withstand voltage 1 min (V) | 2000 | ||||||||||||
Lighting impulse withstand voltage (KV) | 40 | 60 | 75 | 125 | 185 | ||||||||
Local discharge (pc) | ≤10 | ||||||||||||
Dispute bend (N) | ≥1000 | ||||||||||||